Common Mistake: Sizing PDUs by peak wattage without applying the continuous load derate
Event gear often runs 4+ hours straight. Breakers and PDUs must be sized so continuous loads stay at 80% of rating. A 30A 120V circuit caps at 2,880W continuous—not 3,600W. Before finalizing your worksheet, tag every circuit with its continuous limit and mark fixtures accordingly. It’s the fastest way to prevent mid-show breaker trips and uneven phase loading.